How to configure a new ATV in a Unity Pro application ? FORTIS NERA EIP TCP/IP

- open the UP Application

- add ATV device in DTM Browser (ATV9xx in EIP for instance)

- define a device name and an IP

- in the web pages connected to the drive set this IP as static

- then reboot the drive

- connect the DTM

- make a load data from device to be sure you've got the right reference

- configure the following points

- profile as Assembly 100/101

- FDR as enabled stored 10s synchro

- CommandRefParam / Reference source 1 at Embedded Ethernet source

- input phase loss Ignore

- output phase loss ignore



- make a store data to device

- wait the synch is done

- then change the configuration of the FDR from stored to served

- make a store data to device

- rebuild all save and download to the PLC